Ij

Next Page
Previous Page
Table of Contents
PDF Printable
UL Style 3123 Silicone Rubber Insulated
Silicone Rubber
Stranded
Lead Wire
Insulation
Copper
600 Volt, 150º C
DESCRIPTION: UL, CSA Approved, VW-1 Rated. 30 - 16 AWG stranded tinned, nickel or silver plated copper
conductor insulated with 33 mil wall of silicone rubber.
USE: Mercury switch leads and internal wiring of computers and electronic equipment.
CONDUCTOR
Nominal
Equivalent
Circular
AWG of
Nominal
Number of
Nominal Wall
Conductor
AWG Size
Mil Area
Strands
OD
Construction
Strands
Thickness
Diameter
30
19/42
119
19
42
.012
.078
.033
30
11/40
106
11
40
.012
.078
.033
30
7/38
112
7
38
.012
.078
.033
28
65/46
183
65
46
.015
.081
.033
28
40/44
160
40
44
.015
.081
.033
28
19/40
183
19
40
.015
.081
.033
28
7/36
175
7
36
.015
.081
.033
26
66/44
264
66
44
.019
.085
.033
26
19/38
304
19
38
.019
.085
.033
26
7/34
278
7
34
.019
.085
.033
24
3x35/44
420
105
44
.025
.091
.033
24
42/40
404
42
40
.023
.089
.033
24
19/36
475
19
36
.024
.090
.033
24
7/32
448
7
32
.024
.090
.033
22
7x24/44
672
168
44
.032
.098
.033
22
66/40
634
66
40
.029
.095
.033
22
19/34
754
19
34
.030
.096
.033
22
7/30
700
7
30
.030
.096
.033
20
7x37/44
1036
259
44
.040
.106
.033
20
42/36
1050
42
36
.037
.103
.033
20
19/32
1216
19
32
.038
.104
.033
18
7x59/44
1652
413
44
.050
.116
.033
18
7x24/40
1575
168
40
.050
.116
.033
18
65/36
1625
65
36
.047
.113
.033
18
19/30
1900
19
30
.048
.114
.033
16
7x95/44
2660
665
44
.064
.130
.033
16
7x40/40
2691
280
40
.064
.130
.033
16
7x15/36
2625
105
36
.063
.129
.033
w w w. n e w e n g l a n d w i r e . c o m
Te l : 6 0 3 . 8 3 8 . 6 6 2 4
© 2005 New England Wire Technologies
121